How to slove E4 alarm of S&A water chiller CW-5200

Hello, I am Mark from S&A chiller company
Now I show you the troubleshooting of E4 alarm of S&A chiller CW-5200
E4 means room temperature sensor failure alarm
When alarm occurs
The error code and the temperature will be alternately displayed
The alarm sound could be suspended by pressing any button
When E4 alarm occurs
Firstly, find out the connecting terminal of room temp sentor and water temp sentor which are connected with temp controller
Exchange and connect it
If the alarm is suspended we can judge the connecting terminal is loose contact
please connect it correctly
If it is E4 alarm, we can judge the temperature controller is faulted
Please replace it
IF it is E5 alarm, we can judge the room temperature sentor is faulted
Please replace it as well
E4 and E5 alarm occur at the same time
We propose you replace room tempsensor, water temp sensor and temp controller
If you have any question
Feel free to contact S&A after-sales dept.
Thanks for using S&A chiller
chiller
FAX:+86-20-84309967
SKYPE: teyuchiller
Email:marketing@teyu.com.cn  

2016年6月24日星期五

The troubleshooting of E3 alarm of S&A water chiller CW-5200

E3 means over low water temperature alarm
When alarm occurs
The error code and the temperature will be alternately displayed
The alarm sound could be suspended by pressing any button
Under low ambient temperature( e.g. in winter)
When the cooling water temperature is lower than factory setting startup temperature
It is easy to cause E3 alarm
Now I show you the simple troubleshooting of E3 alarm
1、Startup machine(e.g. laser) to rise cooling water temperature
E3 alarm will be automatically eliminated
2、If the chiller works in a larger temperature difference
Add warm water into the water tank until the water temp restore to normal value
E3 water temperature alarm can be eliminated
If the chiller continues alarming
It is possible that temperature controller or sensor is faulted
Feel free to contact S&A after-sales dept.
Thanks for using S&A chiller.
chiller
FAX:+86-20-84309967
SKYPE: teyuchiller
Email:marketing@teyu.com.cn  

2016年6月23日星期四

S&A water cooling system CW-5200 for 3D printing machine

The 3D printing machine is applied in various fields, and it is necessary to be equipped with water cooling system as it will generate heat during working.
A few days ago, a 3D printing machine customer from Czech sent an enquiry to S&A company, and required the pressure of chiller reach 2.2bar. According to the requirement of customer, S&A recommend chiller CW 5300 with 1800W cooling capacity. 
Since January 2016, the warranty period of S&A chiller has extended to 2 years.
Thank you for the trust and support from customers.
chiller
FAX:+86-20-84309967
SKYPE: teyuchiller
Email:marketing@teyu.com.cn