The basic requirement is a nearby water temperature at 16 ° C and a estimated thermal load below 10.000 btu The ambient temperature is air conditioned and close to 25 ° C.
However, for 1000btu (about 3KW) heat load, and water kept at 16C, the cooling capacity of CW-6000 is not sufficient.
According to the cooling performance curves, the cooling capacity is changed according to the ambient temperature and water temperature.
The cooling capacity of CW-6000 is 2.2KW @ 20C ambient and 20C water temp while CW-6200 still has 4.3KW at the same conditions.
Thus we suggest customer to use CW-6200AN230S with gas R410A.
CW-6000 technical parameter:http://www.teyuchiller.com/Products/ChillerCW60003000Wco.html
CW-6200 technical parameter: http://www.teyuchiller.com/Products/ChillerCW62005100Wco.html
TE:+86-20-89301885
FAX:+86-20-84309967
SKYPE:
teyuchiller