2016年9月11日星期日

The troubleshooting of flow alarm of S&A chiller CW-6000

Hello,Iam Jaminy from S&A chiller factory
 
今天为大家介绍
Now, I will show you the troubleshooting
 
遇到特域冷水机CW-6000流量报警时,该如何处理
Regarding the flow alarm of S&A chiller CW-6000
 
特域冷水机CW-6000冷水机出现流量报警
When the flow alarm ocuurs
 
控制面板上会显示E6报警
The panel will display E6 alarm code
 
报警时,出错的代码与水温会交替显示
The error code and the temperature will be alternately displayed 
 
温控器面板上工作状态指示灯ALM OUT灯亮
The "ALM OUT" on
 
指示报警输出状态
It means alarm output status
 
按下任何键可暂停报警声响
The alarm sound could be suspended by pressing any button
 
下面我们来介绍一下冷水机出现流量报警时的具体处理方法
The troubleshooting of flow alarm as below
 
首先,关闭冷水机电源
Firstly, turn off the power supply of machine
 
用短水管将冷水机出水口和入水口短接
Connect a water hose between water inlet and water oulet
 
开启冷水机,继续观察冷水机状况
Turn on the machine and observe the working status
 
若冷水机没有报警
If alarm suspends
 
此时的主要原因是冷水机外部水循环管路不畅通
The outside water circulation pipe is blocked
 
(折弯变形或者堵塞)
The water circulation pipe gets bended or blocked
 
用户可以检查冷水机外部水循环管路
Check the outside water circulation pipe
 
若冷水机继续报警
If the chiller remains alarm
 
此时的主要原因有三个:
The cause as below
 
1、冷水机水箱水位过低
1、Water level inside the tank is too low
 
用户可以检查水位计显示窗
Check the water level gause display
 
加水到水位显示的绿色区域
Add water until the level shown in the green area
 
并检查水循环管路有无漏水
And check whether water circulation pipe leaks
 
2、冷水机内部水循环管道不畅通
2、Internal water circulation pipe is blocked
 
请检查冷水机内部水循环管道
Check the internal water circulation pipe
 
3、冷水机配件出现故障
3、The parts of chiller fault
 
请联系特域冷水机厂家售后服务中心对冷水机配件进行维修或更换
Feel free to contact S&A after-sales dept.
 
感谢大家使用特域冷水机!
Thanks for using S&A chiller
TE:+86-20-89301885