2015年12月30日星期三

S&A 3kW water chiller CW-6000 for cooling magnetic coils

A customer from United States is interested in S&A 3kW water chiller CW-6000 for cooling magnetic coils which are cooled by copper plates with 5 mm inner diameter water cooling lines running through them. The coils dissipate about 800 W total. Ambient temperature 22 degrees C +/- 2 degrees C. Target water temperature: ideally 20 degrees C, but anywhere between 15 C and 30 C is acceptable. Target flow rate approximately 10 Liters/minute, with pressure drop approximately 50 kPa
According to the requirement, S&A chiller CW-5200 is fit for it, which is more cheaper than CW-6000.
water chiller
FAX:+86-20-84309967
SKYPE: teyuchiller

2015年12月29日星期二

S&A industrial chiller is fit for 600W-2000W cooling system

A customer is interested in S&A industrial chiller "CW-3000", "CW-5000" and "CW-5200" to cool a System with a cooling pipeline (diameter 4mm or 6mm). The heating power is 600 W or until 2000 W. The ambient temperature is from 5 °C until +30°C. The target water temperatur is not specifically defined (perhaps 10°C or 20°C) .
-->Water pressure: 2 - 3 bar
-->flow rate: 5 - 10 litre/ minute 
According to the pump performance curves, If the target water temp. is 20°C, for the heating power over 1200W, the right chiller should be CW-6000AIS. So the chiller model CW-5000AI, CW-5200AIS and CW-6000AIS are fit for you.
A means 220V 50Hz;
I means 100W water pump with max. 2.4bar pressure and max. 16L/min flow rate;
S means ozone-friendly gas R-410a.
industrial chiller
FAX:+86-20-84309967
SKYPE: teyuchiller

2015年12月28日星期一

S&A industrial water chiller for Wire EDM machine

A customer is in need of a new water chiller for their Wire EDM machine.  The cooling capacity of chiller require 4.3 to 4.7kw, target temperature of the water is 20 degrees Celsius, flow rate is 20 to 35 l/min and ambient temperature of the room would be approximately 70 degrees F.
According to the information, S&A have two models CW-6200BN250 and CW-6300BN250 for reference.
 
For CW-6200,  according to the cooling performance curve, if the heat load is 4.3KW, under 20C ambient temp, the water temp can be kept at 20C. But when the heat load is 4.7KW, the water temp will be around 26C.
 
The cooling capacity of the chiller changes with different conditions.
 
For CW-6300, it has absolutely sufficient cooling capacity for your requirement. But the air freight of shipping one to USA is very expensive.
So we suggest customer to choose CW-6200 if higher water temp like 26C is acceptable. 
 
Chiller water temp set range: 5C-35C.
Chiller operable ambient temp: max. 45C
water chiller
FAX:+86-20-84309967
SKYPE: teyuchiller