The cooling requirement as below:
1. Heating load vary from 0.5 up to 2.5KW
2. Water temperature required at 17-20?c
However, for max.2.5KW heat load, chiller CW-6000 of 3KW cooling capacity is not able to keep the water temp at 17C-20C according to the cooling performance curve. Hence we recommend chiller model CW-6100 with 4.2KW cooling capacity.
CW-6100 technical parameter: http://www.teyuchiller.com/Products/ChillerCW61004200Wco.html